NIST SP 800-53r5 — PE-15 Water Damage Protection
source: false
type: canonical-control-reference
standard: NIST SP 800-53r5
assessment_standard: NIST SP 800-53Ar5
baseline_standard: NIST SP 800-53B
control_id: "PE-15"
family_id: "PE"
family: "Physical and Environmental Protection"
title: "Water Damage Protection"
status: active
updated: 2026-09-10
authoritative_sources:
- "NIST SP 800-53r5 verified transcription"
- "NIST SP 800-53Ar5 verified transcription"
- "NIST SP 800-53B verified transcription"
baseline_membership:
low: true
moderate: true
high: true
privacy: false
related_controls:
- "AT-03"
- "PE-10"
PE-15 Water Damage Protection
Canonical combined reference
Control text and discussion come from NIST SP 800-53r5; assessment procedures come from NIST SP 800-53Ar5; baseline membership comes from NIST SP 800-53B.
NIST SP 800-53r5 — Control
Protect the system from damage resulting from water leakage by providing master shutoff or isolation valves that are accessible, working properly, and known to key personnel.
Discussion
The provision of water damage protection primarily applies to organizational facilities that contain concentrations of system resources, including data centers, server rooms, and mainframe computer rooms. Isolation valves can be employed in addition to or in lieu of master shutoff valves to shut off water supplies in specific areas of concern without affecting entire organizations.
Related Controls
Supporting Publications
- None specified.
NIST SP 800-53Ar5 — Assessment Procedure
Assessment Objective
Determine if:
-
PE-15[01]— the system is protected from damage resulting from water leakage by providing master shutoff or isolation valves; -
PE-15[02]— the master shutoff or isolation valves are accessible; -
PE-15[03]— the master shutoff or isolation valves are working properly; -
PE-15[04]— the master shutoff or isolation valves are known to key personnel.
Potential Assessment Methods and Objects
Examine
Select from:
- Physical and environmental protection policy.
- procedures addressing water damage protection.
- facility housing the system.
- master shutoff valves.
- list of key personnel with knowledge of location and activation procedures for master shutoff valves for the plumbing system.
- master shutoff valve documentation.
- system security plan.
- other relevant documents or records.
Interview
Select from:
- Organizational personnel with responsibilities for system environmental controls.
- organizational personnel with information security responsibilities.
Test
Select from:
- Master water-shutoff valves.
- organizational process for activating master water shutoff.
References
Source Assessment Procedure — NIST SP 800-53Ar5
NIST SP 800-53B — Baseline Membership
| Baseline | Membership |
|---|---|
| Low | Included |
| Moderate | Included |
| High | Included |
| Privacy | Not included |