NERC CIP — CIP-012-2 R1 Protection of Communications between Control Centers
source: false
type: "canonical-control-reference"
standard: "NERC Critical Infrastructure Protection"
document_version: "CIP-012-2"
criterion_id: "CIP-012-2 R1"
family_id: "CIP-012-2"
family: "Cyber Security – Communications between Control Centers"
title: "Protection of Communications between Control Centers"
status: "active"
assessment_criterion: true
normative_text_included: true
updated: "2026-09-13"
source_pdf: "Resources/CMMC Brain 2.1/Sources/NERC CIP/CIP-012-2.pdf"
source_pages: [2, 3, 5]
requirement_pages: [2, 3]
us_effective_date: "07/01/2026"
mapping_status: "not-transferred-from-2024-SCF-set"
CIP-012-2 R1 Protection of Communications between Control Centers
Version and enforcement
U.S. status checked 2026-09-13: Mandatory Subject to Enforcement. Standard effective date: 07/01/2026. Jurisdiction-specific applicability and transitional obligations must be checked against the implementation plan.
Requirement
The Responsible Entity shall implement, except under CIP Exceptional Circumstances, one or more documented plan(s) to mitigate the risks posed by unauthorized disclosure, unauthorized modification, and loss of availability, of data used in Real-time Assessment and Real-time monitoring while such data is being transmitted between any applicable Control Centers. The Responsible Entity is not required to include oral communications in its plan. The plan shall include: [Violation Risk Factor: Medium] [Time Horizon: Operations Planning]
-
1.1.Identification of method(s) used to mitigate the risk(s) posed by unauthorized disclosure and unauthorized modification of data used in Real-time Assessment and Real-time monitoring while such data is being transmitted between Control Centers;
-
1.2.Identification of method(s) used to mitigate the risk(s) posed by the loss of the ability to communicate Real-time Assessment and Real-time monitoring data between Control Centers;
-
1.3.Identification of method(s) used to initiate the recovery of communication links used to transmit Real-time Assessment and Real-time monitoring data between Control Centers;
-
1.4.Identification of where the Responsible Entity implemented method(s) as required in Parts 1.1 and 1.2; and
-
1.5.If the Control Centers are owned or operated by different Responsible Entities, identification of the responsibilities of each Responsible Entity for implementing method(s) as required in Parts 1.1, 1.2, and 1.3.
Assessment Measure
Examples of evidence may include, but are not limited to, documented plan(s) that meet the mitigation objective of Requirement R1 and documentation demonstrating the implementation of the plan(s). Examples of methods identified in the plan(s) may include, but are not limited to, one or more of the following for each Part:
Part 1.1
- Methods of mitigation used to protect against the unauthorized disclosure and unauthorized modification of the data (e.g., data masking, encryption/decryption) while such data is being transmitted between Control Centers
- Physical access restrictions to unencrypted portions of the network
Part 1.2
- Identification of alternative communication paths or methods between Control Centers
- Procedures explaining the use of alternative systems or methods for providing for the availability of the data
- Service level agreements with carriers containing high availability provisions
- Availability or uptime reports for equipment supporting the transmission of Real-time Assessment and Real-time monitoring data
Part 1.3
- Contract, memorandum of understanding, meeting minutes, agreement or other information outlining the methods used for recovery
- Methods for the recovery of links such as standard operating procedures, applicable sections of CIP-009 recovery plan(s), or similar technical recovery plans
- Documentation of the process to restore assets and systems that provide communications
- Process or procedure to contact a communications link vendor to initiate and or verify restoration of service
Part 1.4
- Descriptions or logical diagrams indicating where the implemented methods reside
- Identification of points within the infrastructure where the implemented methods reside
- Third party Agreements detailing where the methods are implemented if such methods are implemented by the third party
Part 1.5
- Contract, memorandum of understanding, meeting minutes, agreement, or other documentation outlining the responsibilities of each entity
Violation Severity Levels
Lower
N/A
Moderate
The Responsible Entity documented its plan(s), but failed to include one of the applicable Parts of the plan as specified in Requirement R1.
High
The Responsible Entity documented its plan(s), but failed to include two of the applicable Parts of the plan as specified in Requirement R1.
Severe
The Responsible Entity failed to document its plan(s) for Requirement R1;
Or
The Responsible Entity failed to implement three or more Parts of its plan(s) for Requirement R1, except under CIP Exceptional Circumstances.
Applicability and Evidence Retention
CIP-012-2 applicability, exemptions, compliance monitoring, and evidence retention.
Referenced Publications
- CIP-012-2 official standard; PDF page(s) 2, 3, 5. NERC original PDF.
- NERC standard status and dates (checked 2026-09-13).
- CIP-012-2 implementation plan. NERC original implementation plan.
Notes
- Assessment reference scope: the complete numbered requirement, associated parts and measures are kept together. Source wording is transcribed; line wrapping and presentation are normalized. The official PDF controls if a discrepancy is found.
- Table columns are presented as labeled subsections for each part so applicability, requirements, and measures remain associated.
- Publicly available does not mean public domain. This is an internal reference, not an NERC publication or endorsement.
- Legacy SCF relationships refer to the 2024 versioned mapping set; no cross-version equivalence is asserted.