CIP-005-8 R1 Electronic Security Perimeter
Version and enforcement
U.S. status checked 2026-09-13: Subject to Future Enforcement. Standard effective date: 07/01/2028. Jurisdiction-specific applicability and transitional obligations must be checked against the implementation plan.
Requirement
Each Responsible Entity shall implement one or more documented processes that collectively include each of the applicable requirement parts in CIP-005-8 Table R1 – Electronic Security Perimeter. [Violation Risk Factor: Medium] [Time Horizon: Operations Planning and Same Day Operations].
Assessment Measure
Evidence must include each of the applicable documented processes that collectively include each of the applicable requirement parts in CIP-005-8 Table R1 – Electronic Security Perimeter and additional evidence to demonstrate implementation as described in the Measures column of the table.
Requirement Parts
Part 1.1
Applicable Systems
High impact BCS and their associated PCA
Medium impact BCS and their associated PCA
Requirement
Applicable Systems connected to a network via a routable protocol must be protected by an ESP.
Measures
Examples of evidence may include, but is not limited to, a list of all ESPs with all uniquely identifiable applicable Cyber Systems connected via a routable protocol within each ESP.
Part 1.2
Applicable Systems
High impact BCS with ERC and their associated PCA
Medium impact BCS with ERC and their associated PCA
Requirement
Permit only needed routable protocol communications, documenting the reason, and deny all other routable protocol communications, through the ESP; excluding time sensitive communications of Protection Systems.
Measures
Examples of evidence may include, but are not limited to, documentation that includes the configuration of system and documented reason, such as:
- Electronic Access Point (EAP) configuration;
- Network infrastructure configuration (e.g., technical policies, ACL, VLAN, VXLAN, MPLS, VRF, multi-context, or multi- tenant environment); or
- SCI configuration or settings (e.g., technical policies, hypervisor, fabric, back-plane, or SAN configuration).
Part 1.3
Applicable Systems
SCI supporting an Applicable System from Part 1.1.
EACMS, and their supporting SCI, that control an ESP for an Applicable System in
Part 1.1
Requirement
Protect ESP and SCI configurations by implementing methods to permit only needed network accessibility to Management Interfaces of Applicable Systems, per system capability.
Measures
Examples of evidence may include, but are not limited to, documentation of the methods implemented to permit only needed network accessibility to Management Interfaces, including documented reasons such as:
- Logical configuration or settings (e.g., technical Policies, ACL, VLAN, VXLAN, MPLS, VRF, multi-context, or multi-tenant environment);
- Physically isolated or out-of-band network for dedicated Management Interfaces; or
- SCI configuration or settings showing the isolation of the Management Interfaces (e.g., technical policies, hypervisor, fabric back-plane, or SAN configuration).
Part 1.4
Applicable Systems
High impact BCS and their associated PCA
Medium impact BCS and their associated PCA
SCI supporting an Applicable System in this Part
Requirement
Perform authentication when establishing Dial-up Connectivity with Applicable Systems, if any, and per system capability.
Measures
Examples of evidence may include, but are not limited to, configuration, settings, or documented process that describes how the Responsible Entity is providing authenticated access through each dial-up connection.
Part 1.5
Applicable Systems
High impact BCS
Medium impact BCS at Control Centers
Requirement
Have one or more methods for detecting known or suspected malicious routable protocol communications entering or leaving an ESP.
Measures
An example of evidence may include, but is not limited to, documentation that malicious routable protocol communications detection methods (e.g., intrusion detection system, application layer firewall, etc.) are implemented.
Part 1.6
Applicable Systems
High impact BCS and their associated PCA
Medium impact BCS at Control Centers and their associated PCA
Requirement
Protect the data traversing communication links used to span a single ESP between PSPs through the use of:
- Confidentiality and integrity controls, or
- Physical controls that restrict access to the cabling and other non-programmable communication components in those instances when such cabling and components are located outside of a PSP,
Excluding:
-
i.Real-time Assessment and Real-time monitoring data while being transmitted between Control Centers subject to CIP-012; and
-
ii.Time-sensitive communication of Protection Systems.
Measures
Examples of evidence may include, but are not limited to, documentation of methods used to protect the confidentiality and integrity of the data, such as:
- Configurations or settings used to enforce encryption; or
- The physical access restrictions (e.g., cabling and components secured through conduit or secured cable trays).
Violation Severity Levels
Lower
Not specified in the source table.
Moderate
Not specified in the source table.
High
The Responsible Entity did not have a method for detecting known or suspected malicious routable protocol communications entering or leaving the ESP required by Part 1.5.
OR
The Responsible Entity did not document the reason for permitting communications. (Part 1.2)
Severe
The Responsible Entity did not document one or more processes for CIP-005-8 Table R1 – Electronic Security Perimeter. (R1)
OR
The Responsible Entity did not protect the Applicable Systems connected to the network with routable protocol with an ESP. (Part 1.1)
OR
The Responsible Entity did not permit only needed communications and deny all other communications, through the ESP; excluding time sensitive communications of Protection Systems. (Part 1.2)
OR
The Responsible Entity did not protect ESP and SCI configurations by implementing methods to permit only needed network accessibility to Management Interfaces for Applicable Systems per system capability. (Part 1.3)
OR
The Responsible Entity did not perform authentication when establishing Dial-up Connectivity with the Applicable Systems. (Part 1.4)
OR
The Responsible Entity did not implement a method to protect the data traversing communication links, used to span a single ESP between PSPs, as required by Part 1.6.
Applicability and Evidence Retention
CIP-005-8 applicability, exemptions, compliance monitoring, and evidence retention.
Referenced Publications
- CIP-005-8 official standard; PDF page(s) 4, 5, 6, 12, 13. NERC original PDF.
- NERC standard status and dates (checked 2026-09-13).
- CIP-005-8 implementation plan. NERC original implementation plan.
Notes
- Assessment reference scope: the complete numbered requirement, associated parts and measures are kept together. Source wording is transcribed; line wrapping and presentation are normalized. The official PDF controls if a discrepancy is found.
- Table columns are presented as labeled subsections for each part so applicability, requirements, and measures remain associated.
- Publicly available does not mean public domain. This is an internal reference, not an NERC publication or endorsement.
- Legacy SCF relationships refer to the 2024 versioned mapping set; no cross-version equivalence is asserted.