NERC CIP — CIP-014-4 R3 Risk Assessment Methodology


source: false

type: "canonical-control-reference"

standard: "NERC Critical Infrastructure Protection"

document_version: "CIP-014-4"

criterion_id: "CIP-014-4 R3"

family_id: "CIP-014-4"

family: "Physical Security"

title: "Risk Assessment Methodology"

status: "approved-future-enforcement"

assessment_criterion: true

normative_text_included: true

updated: "2026-09-13"

source_pdf: "Resources/CMMC Brain 2.1/Sources/NERC CIP/CIP-014-4.pdf"

source_pages: [2, 3, 11]

requirement_pages: [2, 3]

us_effective_date: "10/01/2028"

mapping_status: "not-transferred-from-2024-SCF-set"


CIP-014-4 R3 Risk Assessment Methodology

Version and enforcement

U.S. status checked 2026-09-13: Subject to Future Enforcement. Standard effective date: 10/01/2028. Jurisdiction-specific applicability and transitional obligations must be checked against the implementation plan.

Requirement

Each Transmission Owner shall have a documented risk assessment methodology for evaluating the loss of each applicable Transmission station or Transmission substation identified in Requirement R1. The methodology shall include, at a minimum, the following: [Violation Risk Factor: High; Time-Horizon: Long-term Planning]

    - **`3.3.1.`** At the applicable Transmission station or Transmission substation:
        - **`3.3.1.1.`** Prior loss of communication and Protection Systems;
        - **`3.3.1.2.`** Application of a Fault or Faults; and
        - **`3.3.1.3.`** Delayed (remote) clearing times shall be used unless otherwise technically substantiated.
    - **`3.3.2.`** At each proximate existing BES station(s) and BES substation(s), as applicable:
        - **`3.3.2.1.`** Application of a Fault or Faults, either simultaneous with or following the Fault or Faults applied under Part 3.3.1.2; and
        - **`3.3.2.2.`** Normal clearing times shall be used unless otherwise technically substantiated.
    - **`3.3.3.`** A documented justification for the Fault(s) associated with physical attack to be simulated. A single justification may be used for multiple locations. The justification shall include at a minimum:
        - **`3.3.3.1.`** The type of credible high-severity physical attack considered; and
        - **`3.3.3.2.`** The type of Fault(s) selected based upon the attack considered.
    - **`3.3.4.`** Removal of all Elements that Protection Systems and other controls are expected to automatically disconnect.
    - **`3.3.5.`** Actual or more conservative clearing times shall be used.

Assessment Measure

Each Transmission Owner shall provide dated evidence, such as electronic or hard copies, of a risk assessment methodology satisfying Requirement R3.

Violation Severity Levels

Lower

N/A

Moderate

The Transmission Owner has a risk assessment methodology that failed to include one of the requirements listed in Parts 3.1 through 3.3.

High

The Transmission Owner has a risk assessment methodology that failed to include two of the requirements listed in Parts 3.1 through 3.3.

Severe

The Transmission Owner has a risk assessment methodology that failed to include all three of the requirements listed in Parts 3.1 through 3.3. OR The Transmission Owner does not have a risk assessment methodology.

Applicability and Evidence Retention

CIP-014-4 applicability, exemptions, compliance monitoring, and evidence retention. Integral attachment(s): CIP-014-4 R1 attachments.